Back to top
Send SMS
+918045804429
6 - 10 kVA Standalone UPS System

6 - 10 kVA Standalone UPS System

72000 INR/Unit

Product Details:

X

Price And Quantity

  • 1 Unit
  • 72000 INR/Unit

Product Description

6 - 10 kVA Standalone UPS System that presented by us meets the power backup requirement of diverse Companies / Industries across verticals. This type of uninterruptible power supply solution system is engineered and manufactured by well-experienced technocrats and dedicated personnel using components & parts of the best quality in complete line with electrical & electronic industry norms & standards. Portable, highly energy efficient, high performance and low maintenance, the 6 - 10 kVA Standalone UPS System can easily be availed from us in different sizes, powers, capacities and models.

Technical specifications :

GENERAL DATA

6000 VA

10000 VA

Output rated power [W]

5400 W

9000 W

Output power factor 0.9

Topology True online double conversion

Inbuilt batteries No

INPUT

  • Nominal input voltage 200 / 208 / 220 / 230 / 240 Vrms
  • Input voltage tolerance 110-276 Vac (depending on the load)
  • Input current THD <5% at 100% load
  • Frequency range 45-55 Hz / 54-66 Hz
  • Power factor ≥0.99

OUTPUT

  • Rated output voltage 208 / 220 / 230 / 240 VAC
  • Voltage tolerance <1% (static and dynamic) (referred to 230 V)
  • Voltage distortion <2% linear load, <5% non-linear load (IEC / EN62040-3)
  • Overload capability Normal mode:
  • 10 min.:105%-125% / 1 min.:125%-150% / 10s.:150-170% / 100ms.: >170% (0-35ºC)
  • 2 min.:105%-125% / 30 s.:125%-150% / 100 ms.: >150% (35-45 ºC)
  • Battery mode:
  • 2 min.:105%-125% / 30 s.: 125%-150% / 100 ms.: >150%
  • Nominal frequency 50Hz or 60Hz ±0.05Hz
  • Frequency tolerance 45-55 Hz /54-66 Hz
  • Crest Factor 3:1

TRANSFER TIME

  • Battery <–> inverter 0 ms
  • Bypass <–> inverter 0 ms
  • Inverter to Eco-mode 0 ms
  • Eco-mode to inverter <10 ms

EFFICIENCY

  • AC-AC Up to 92%
  • In eco-mode Up to 96%

ENVIRONMENT

  • Protection rating IP 20
  • Storage temperature -15 - +60°C
  • Operating temperature 0 - 45°C
  • Relative humidity 0 - 95% (Non-condensing)
  • Altitude (above sea level) 1000 m without de-rating

BATTERIES

  • Types VRLA, vented lead-acid, NiCd
  • Battery charger 4 A

COMMUNICATIONS

  • User interface LCD display
  • Communication cards (option) SNMP, AS400, Relay card

COMPLIANCY

  • Safety IEC / EN 62040-1
  • EMC IEC / EN 62040-2
  • Performance IEC / EN 62040-3
  • Manufacturing ISO 9001:2008, ISO 14001:2004

WEIGHT, DIMENSIONS

Weight

25.5 kg

29.5 kg

Dimensions

WxHxD 260 x 708 x 550 mm


AURO POWER SYSTEMS